Name:

AnalogInput01 to AnalogInput04

名称:

AnalogInput01 to AnalogInput04

 

Depending on the configuration, these registers contain

The actual input value of the associated input averaged over the last 8 samples

Or the characteristic value to be calculated using the configured number of samples

The value in the register is scaled according to the configuration of register AnalogInputScale.

If scaling the value takes it outside of the permissible range of values for INT, then it will be limited to the minimum or maximum INT value. The overflow bit for the corresponding channel is not set in this case.

 

根据配置,这些寄存器包含

在最后8个样本上相关输入的实际输入值的平均值

或者使用配置的样本数量计算的特征值

这个寄存器中的值根据 AnalogInputScale寄存器的配置进行比例缩放。

如果按比例缩放该值,但超出 INT 值的允许范围,则它将被限制为INT值的最小值或最大值。在这种情况下,对应通道的溢出位不置位。

 

Information:

说明:

 

In Function model 0 - Standard, Automation Runtime automatically scales the analog input to mg or non-dimensional values (crest factor) while taking SensitivitySensor and AnalogInputScale into account. If the value of AnalogInput without sensor scaling exceeds the value range of AnalogInputScale related to 100 mV/g, the corresponding AnalogInputOverflow bit is set.

 

Function model 0 - Standard, Automation Runtime 自动将模拟量输入缩放为 mg 或 无量纲值(波峰因数(裕度),crest factor),同时考虑SentivitySensor(传感器灵敏度) 和 AnalogInputScale(模拟量输入比例)。如果传感器不带缩放的 AnalogInput 模拟量输入值,超过了 AnalogInputScale 与 100 mV/g 相关的值范围,则置位相应的 AnalogInputOverflow 溢出位。

 

Data type

数据类型

Values

INT

-32768 to 32767