模拟量输入配置 - AnalogInputConfig

<< 点击显示目录 >>

主页  振动监测 > X20(c)CM4810使用手册 > 寄存器说明 - Register description  > 模拟量输入功能 - Analog input functions  >

模拟量输入配置 - AnalogInputConfig

 

Name:

AnalogInputConfig01

名称:

AnalogInputConfig01

 

Register for configuring the characteristic value calculation in AnalogInput. This is only needed if SamplesAnalogInput of the respective channel is greater than 0.

用于在 AnalogInput中配置特征值计算的寄存器。 只有当相应通道的SamplesAnalogInput 大于 0 时,才需要配置。

Data type

数据类型

Values

Bus controller default setting

总线控制器默认设置

UINT

See the bit structure.

请参阅位结构。

0

 

位结构:

Bit

Description

描述

Value

Description

描述

0 - 1

Value to be calculated in AnalogInput01

在模拟量输入 AnalogInput01 中要计算的值

0

Mean value (bus controller default setting)

平均值 (总线控制器默认设置)

1

Peak value

峰值

2

RMS value

有效值

3

Crest factor

波峰因数(裕度)

2 - 3

Value to be calculated in AnalogInput02

在模拟量输入 AnalogInput02 中要计算的值

x

For possible values, see bits 0-1.

见 bits 0-1.

4 - 5

Value to be calculated in AnalogInput03

在模拟量输入 AnalogInput03 中要计算的值

x

For possible values, see bits 0-1.

见 bits 0-1.

6 - 7

Value to be calculated in AnalogInput04

在模拟量输入 AnalogInput04 中要计算的值

x

For possible values, see bits 0-1.

见 bits 0-1.

8

Trigger mode of AnalogInput01

AnalogInput01 的触发模式

0

Continuous with enable (bus controller default setting)

带使能的连续触发(总线控制器默认设置)

1

Once with trigger

单次触发

...

 

...

 

11

Trigger mode of AnalogInput04

AnalogInput04 的触发模式

0

Continuous with enable (bus controller default setting)

带使能的连续触发(总线控制器默认设置)

1

Once with trigger

单次触发

12

Signal source for characteristic value calculation AnalogInput01

用于特征值计算的信号源 AnalogInput01

0

Raw signal filtered to the configured maximum frequency (see MaxFrequencyRaw) with mean value adjustment.1) (Bus controller default setting)

滤波到配置的最大频率的原始信号 (see MaxFrequencyRaw) ,并进行平均值调整。1) (总线控制器默认设置)

1

Raw signal filtered to 10 kHz without mean adjustment

滤波到 10kHz 的原始信号,无均值调整

...

 

...

 

15

Signal source for characteristic value calculation of AnalogInput04

用于特征值计算的信号源 AnalogInput04

0

Raw signal filtered to the configured maximum frequency (see MaxFrequencyRaw) with mean value adjustment.1) (Bus controller default setting)

滤波到配置的最大频率的原始信号 (see MaxFrequencyRaw) ,并进行平均值调整。1) (总线控制器默认设置)

1

Raw signal filtered to 10 kHz without mean adjustment

滤波到 10kHz 的原始信号,无均值调整

1)

The average of the last 8192 samples is used for mean adjustment.

最后 8192 个样本的平均值被用于均值调整。