The input high-pass cutoff frequency of the AC voltage input (limit frequency of 34 MHz) means that a certain amount of settling time is required after changing the DC offset of the pending signal.
交流电压信号输入的输入高通截止频率(极限频率为 34 MHz)意味着在改变待定信号的直流偏移后需要一定的建立时间。
•Settling time of approximately 30 seconds at 100 mV/g sensor sensitivity and a 24 V supply voltage with an accuracy of 0.4 g
在 100 mV/g 传感器灵敏度和 24V 电源电压下,精度为 0.4 g,整定时间约为 30 秒
•Settling time of approximately 60 seconds at 100 mV/g sensor sensitivity and a 24 V supply voltage with an accuracy of 0.001 g
在 100 mV/g 传感器灵敏度和 24V 电源电压下,精度为 0.001 g,整定时间约为 60 秒
•The respective settling time must be allowed to pass in order to achieve accurate measurement results when an open line occurs. Because of this, all characteristic values and analog input values are set to 0 by the module during the first 30 seconds after a restart or wire breakage.
必须允许各通过自的整定时间,以便在出现开路时获得准确的测量结果。因此,在重启或断线后的前30秒内,模块将所有特征值和模拟输入值设置为0。