The following formulas can be used to convert the raw value into a vibration value [mg]:
Information:
The maximum resolution always depends on the sensor used. The module operates in the range of ±10 V. For a 100 mV/g sensor, this corresponds to a maximum value of ±100 g. With a 50 mV/g sensor, the maximum value is ±200 g.
Example
A 100 mV/g sensor is used; the module provides the value 4608 as a raw value and the data resolution is configured to 24 bits. This results in the following values for the calculation:
•Raw value = 4608
•MaximumValue_10V_AnalogIn= 10 V (module value, cannot be changed)
•MaximumValue_10V_Digitalin with 24 bits = 8388607 (see Data resolution)
•Sensor resolution = 100 mV/g = 0.1 V/g = 0.0001 V/mg